Extinguishing
Configuring the forwarding of the extinguishing released state
16
393 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
7. Use 'Assign' to assign the relevant 'Extinguishing reporting zone' element of the
flooding zone from the detection tree to the 'Causes' element. To do this, select
the ' --Pre-ALARM, extinguishing' event category on the left in the 'Assign'
dialog and then select the corresponding 'Extinguishing reporting zone' element
of the flooding zone on the left in the detection tree.
8. Highlight the 'Effects' element under the 'Fire control' element no. 1.
9. Use 'Assign' to assign any free output to the 'Effects' element. For example,
this could be an output on the periphery board of the station or an output on an
input/output module of a line card.
10. Under the 'Fire control group' element, create a new 'Fire control' element with
the template ID '1 -- Standard Fire control'.
Information: This element is referred to as ''Fire control' element no. 2' below.
Information: This 'Fire control' element no. 2 transmits a potential 'Isolation'
state of the 'Fire control' element no. 1 to the flooding zone control.
11. Highlight the new 'Fire control' element no. 2 in the control tree.
12. Amend the customer text in the 'Overview' tab if necessary.
13. Configure the 'Fire control' element no. 2 in the 'Details' tab according to the
'Fire control' element no. 2 for transmitting the 'Isolation' state' column in the
table later on in this chapter. Link [
14. Highlight the 'Causes' element under the 'Fire control' element no. 2.