'Hardware' task card
C-NET detector line
10
128 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
Parameters
Value
Description
'ALERT tone'
'1: Continuous, 970Hz [BS
5839]'
The parameter defines the alarm tone that the
sounder plays when active.
The alarm tones are standardized. The values in
brackets refer to the underlying standard or
guideline.
You will find information on the characteristics of the
alarm tones in the documentation for the sounder
and sounder base in question. See chapter
'Applicable documents'.
'2: Intermittent, 950Hz [BS
5839]'
'3: Sweep-down, 1200-
>540Hz [DIN33404]'
'4: Slow-whoop, 540-
>1200Hz [NEN2575]'
'5: Pulse-tone, 500Hz [SS
03 17 11]'
'6: Intermittent, 500Hz [SS
03 17 11]'
'7: Continuous (30s),
500Hz [SS 03 17 11]'
'8: Alternating, 560/440Hz
[NF S 32-001]'
'9: Intermittent, 420Hz [AS
2220]'
'10: Slow-whoop, 540-
>1200Hz [AS 2220]'
'11: Intermittent, 970Hz
[ISO 8201]'
'12: Sweep 800->970Hz,
7/s [BS Fire tone]'
'13: Sweep 150->1000-
>150Hz, 10s/40s/10s [DE
Industrial alarm]'
'14: Intermittent, 520Hz
[Temporal 3/ISO8201]'
'15: School bell'
'31: Mute'
'EVAC tone'
The alarm tones that can
be selected correspond to
those under 'ALERT tone'.
The parameter defines the alarm tone during the
evacuation phase.
The alarm tones are standardized. The values in
brackets refer to the underlying standard or
guideline.
You will find information on the characteristics of the
alarm tones in the documentation for the sounder
and sounder base in question. See chapter
'Applicable documents'.
'Sounder volume'
'High'
This parameter defines the sound level for the alarm
tone.
'Medium'
'Low'
See also
2
Prioritized voice evac. control [
2