Configuration –Overview
Without pre-configuration
9
115 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
9.2 Without pre-configuration
During commissioning, first the components and the
'Station' periphery are read
in. There are two ways of reading in the periphery:
●
The C-NET detector lines are read in individually. The resultant physical
structure is loaded in Cerberus-Engineering-Tool. Afterwards, the logical
structure is created in Cerberus-Engineering-Tool and assigned to the physical
structure.
●
The C-NET detector lines are read in by auto-configuration. This results in the
physical structure and the logical structure. The two structures are loaded to
Cerberus-Engineering-Tool.
Auto-configuration can be performed for the 'Station' or for individual
detector
lines.
9.3 Customer text
Customer text can be entered for each element in the structure tree. The customer
text is shown on the display of a
'Station'. The length of the customer text is
checked during entry.
Customer text is displayed in accordance with the following rules:
Elements except 'Zone' element
If a message associated with an element appears, the corresponding customer text
is displayed. If no customer text is assigned to the element, the customer text of
the superordinate element is displayed with a customer text.
Example: If a
'Section' has no customer text, then the customer text of the
'Detection area' is displayed.
'Zone' element
If an alarm message for a
'Zone' appears, the customer text of the detector
sensor assigned to it is displayed. If the assigned detector sensor is not assigned
any customer text, the customer text for the 'Zone' is displayed. If no customer text
is assigned to the 'Zone' either, the customer text of the next superordinate
element appears.