'Control' task card
Input/output module FDCIO223 with monitored input/output
12
251 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
'Activation timeout 'unmanned'':
This setting specifies the duration of the time-out in 'Unmanned operation'. The
time-out is started when the control is activated. After the expiration of the set time,
the sounder is deactivated automatically.
NOTICE
Incorrect cause assignment for 'Activation timeout 'manned'' / 'Activation timeout
'unmanned''
The 'Activation timeout 'manned'' / 'Activation timeout 'unmanned'' sounder
property is only evaluated for one 'Area' element in the detection tree or for
elements within one 'Area' element.
w
One or more sounders are assigned as 'Control'
element effects.
w
The 'Activation timeout 'manned'' property and / or 'Activation timeout
'unmanned'' is active.
●
Only assign one 'Area' element or elements from one 'Area' element as the
cause of the 'Control'.
You will find a description of the properties in the 'Hardware' tab in chapter
'Input/output module FDCIO223 [
You can also set the properties in the 'Hardware' task card.
You will find more information on input / output module FDCIO223 in document
009122. See chapter 'Applicable documents'.
See also
2
Input/output module FDCIO223 [
2
12.11 Input/output module FDCIO223 with monitored
input/output
You can configure the two inputs / outputs of the input / output module FDCIO223
as monitored inputs and / or outputs.
You can assign one monitored input as cause for the following controls:
●
'Fire control'
●
'Universal sounder evac control'
●
'Phased sounder evac control'
You can assign one monitored output as an
effect for the following control:
●
'Fire control'
You will find more information on input / output module FDCIO223 in document
009122. See chapter 'Applicable documents'.
See also
2
Input/output module FDCIO223 [
2