CF-71 sets the display when the minimum value is output.
CF-72 sets the display when the maximum value is output.
Example:
CF-71: Set to 1 000
CF-72: Set to 5 000
The maximum value is output when the display is 5 000.
The minimum value is output when the display is 1 000.
Analog output
Approx. 21.6 mA
Approx. 11 V
20 mA
10 V
Maximum display
4 mA
0 V
Minimum display
1000
Approx.2.4 mA
Approx. -1 V
5000
Display
5500
-10 % of the maximum display
Note:
-
The CF-72 setting must not exceed the maximum load, as described in Chapter
.
-
The CF-71 setting must be less than the CF-72 setting.
18.1.6
Analog output ine calibration
After the analog output scaling is executed by setting C function CF-71 and CF-72, the ine
adjustment is executed by the trimmer ZERO and the trimmer SPAN.
The ine adjustment range is approx. ±10 % of full scale.
ZERO trimmer
SPAN trimmer
ZERO SPAN
A-OUT
F.G.
Weight indicator CSD-903
18 Options
EN-168
Minebea Intec