4.4.2
Output connection
B1
Output 1
B2
Output 2
B3
Output 3
B4
Output 4
B5
Output 5
B6
Output 6
B7
Output 7
B8
Output 8
B9
Output 9
B10
Output 10
B11
Output 11
B12
Output 12
A12
Output 13
Surge elimination device
V
CE
Load
B1 to B11
B12
COM 2
Open collector rating:
V
CE
= 35 V DC, I
C
= 40 mA DC
A11
COM 2
Note:
-
The external control output common is insulated from the other commons.
-
Connect a suitable surge elimination device for load protection from external
control output.
4.5 Connecting to a 2-pin method serial interface
The 2-pin method serial interface is used to connect to printers, external display units,
etc.
The 2-pin method serial interface is connected with +, - and F.G., as shown in the below
igure.
S.G.F.G.
+
–
A
B
+12 V
470
S-I/F RS-485
Applicable plug:
XW4B-06B-H1
(by OMRON)
CSD-903 internal equiva-
lent circuit
2-pin method serial
interface
corresponding
equipment