Extinguishing
Configuring flooding zone control
16
355 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
Main features and typical
application
Typical event category
Event text
1
' ----Other extinguishing fault'
'PressureSw.timeout'
'Module reset req.'
'Input / output'
'Output fuse fault'
'X-bus fault'
'Configurat. fault'
'Fault aux.function'
' --Earth fault'
'Earth fault ($(POLARITY))'
' --Control test mode'
'Control test mode'
'System information'
'Module config.runs'
Table 22: Properties of the template
1
Text that is shown on the display of the Person Machine Interface when the event
occurs.
Creating and configuring the 'Extinguishing sector control'
The sequence only contains the necessary configuration steps. You will find
information about the elements that can be assigned or created, as well as the
parameters, in separate sections further down in this chapter.
w
An 'Extinguishing control group' element is created in the 'Control tree'. You will
find information on creating an 'Extinguishing control group' element in chapter
'Configuring an extinguishing control group [
1. Create an 'Extinguishing sector control' element under the 'Extinguishing
control group' element.
a
The template creates an 'Extinguishing sector control' element.
a
The template automatically creates two zone elements for 'Causes' and
'Effects' under the 'Extinguishing sector control' element. 'Causes' functions
and 'Effects' functions which have already been pre-configured can be
found within the zones.
2. Enter the required customer text in the 'Overview' tab.
3. Configure the 'Extinguishing sector control' element in the 'Overview' tab.