'Control' task card
Evac control group
12
228 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
Parameters
Values
Description
'Pre-announce tone'
'1: Continuous, 970Hz [BS
5839]'
An alarm tone with the selected characteristics is
played before the voice message.
The alarm tones are standardized. The values in
brackets refer to the underlying standard or
guideline.
You will find information on the characteristics of the
alarm tones in the documentation for the sounder
and sounder base in question. See chapter
'Applicable documents'.
'2: Intermittent, 950Hz [BS
5839]'
'3: Sweep-down, 1200-
>540Hz [DIN33404]'
'4: Slow-whoop, 540-
>1200Hz [NEN2575]'
'5: Pulse-tone, 500Hz [SS
03 17 11]'
'6: Intermittent, 500Hz [SS
03 17 11]'
'7: Continuous (30s),
500Hz [SS 03 17 11]'
'8: Alternating, 560/440Hz
[NF S 32-001]'
'9: Intermittent, 420Hz [AS
2220]'
'10: Slow-whoop, 540-
>1200Hz [AS 2220]'
'11: Intermittent, 970Hz
[ISO 8201]'
'12: Sweep 800->970Hz,
7/s [BS Fire tone]'
'16: Sweep 800->970Hz,
1s [IT Alert]'
'13: Sweep 150->1000-
>150Hz, 10s/40s/10s [DE
Industrial alarm]'
'14: Intermittent, 520Hz
[Temporal 3/ISO8201]'
'15: School bell'
'31: Mute'