'Hardware' task card
C-NET detector line
10
126 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
'Flashing pattern'
This setting specifies the flashing pattern of the beacon. If you select a flashing
pattern with a self-test function, then the beacon will light up briefly every couple of
hours. If you do not want the beacon to light up during
normal operation, then
you must select a flashing pattern without self-test function.
This property is available only for DBS728 and DBS729.
You will find additional information on the interbases and alarm sounders in the
following documents:
FDS221: Document 008109
FDS229: Document 010095
DBS721 and DBS729: Document A6V10320094
See chapter 'Applicable documents'.
See also
2
10.3.7 Sounders and sounder bases (sounders, sounder
beacons, voice sounders)
You are able to configure the properties for the following sounders and sounder
bases in the detail editor:
●
Sounders: FDS224, FDS225, FDS226, FDS227
●
Sounder bases: FDB226, FDB227, FDSB226, FDSB227
Configuring sounders and sounder bases
w
A configuration is loaded into Engineering Tool.
w
The configuration contains at least one of the sounders or sounder bases listed
above.
1. Select the 'Hardware' task card.
2. In the tree view, open the following:
'Station' >
line card >
loop or
stub
3. Open an element for the sounders or sounder bases listed above.
4. Under the sounder element, highlight the element 'Voice sounder', 'Sounder
beacon', or 'Voice sounder beacon'.
5. Configure the element in the 'Overview' tab.