'Control' task card
Evac control group
12
211 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
'Phased voice evac control' – 'Causes' elements – parameters in the
'Details' tab
The parameters described below are not available or cannot be configured in
every 'Causes' element.
Parameters
Value
Description
'Reactivation upon
unsuccessful reset'
On/off
This setting determines whether the system is to
reactivate an already deactivated control again if the
event that triggered the control was not able to be
successfully reset. Note: The system evaluates this
parameter at the exact time of the reset attempt.
Checkbox activated: The system handles the event
as a new event and reactivates the control.
Checkbox deactivated: The system does not handle
the event as a new event and does not reactivate the
control.
'Phased voice evac control' – 'Causes' assignments – parameters in
the 'Overview' tab
The parameters described below are not available or cannot be configured for
every 'Causes' assignment.
The following table describes possible parameters in the 'Overview' tab for
'Causes' assignments:
Parameters
Values
Description
'Delay'
Input field for time period
[hh:mm:ss]
Adjustment range: 0...120
min
Increments: 30 sec
The parameter determines the length of the
activation delay by the control for the respective
effects when the activation conditions of the
assigned cause have been met.
Example: If, for example, an input is assigned as the
cause and the control evaluates it as 'active', then
the activation condition of this cause has been met.
The control delays the activation of the relevant
control effects from this point by the time set in this
parameter.
'Evaluation filter time'
Input field for time period
[hh:mm:ss]
Adjustment range: 0...5
min
Increments: 1 sec
This parameter specifies the length of time the signal
of the assigned input must be active until the control
evaluates it as active.