'Control' task card
Extinguishing standard interface SST [DE]
12
244 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
Assigning 'Input 'Discharged''
An input of the input/output module serves is used to confirm extinguishing
activated.
Figure 72: 'Assign dialog' window for assigning the 'Input 'Discharged'' element
To assign 'Input 'Discharged'', proceed as follows:
1. Select the 'Detection' task card.
2. Open the
'Station' in the tree view.
3. Highlight a
'Section' and create an 'XC10 zone' element.
4. Open 'XC10 zone' and highlight 'Input 'Discharged''.
5. Open the 'Assign dialog' window.
a
'Input 'Discharged'' is highlighted and the 'Hardware tree' appears. The
elements that can be assigned are highlighted.
6. In the 'Assign dialog' window, select the relevant 'Input' of input/output module
FDCIO224 and click on 'Assign'.
a
'Input 'Discharged'' is assigned to the 'Input'.