Extinguishing
Configuring flooding zone control
16
360 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
9. Assign the associated input, to which the manual call points are connected, on
the extinguishing card to the 'Manual release' function with 'Assign'. This could
be a 'Collective input', for example.
10. Highlight the assigned 'Input' element and enter the required customer text in
the 'Overview' tab.
11. Configure the assigned 'Input' element in the 'Overview' tab.
12. Assign the input type to the assigned element in the 'Hardware' tab under
'Extinguishing input type'. You will find information about the selectable input
types in chapter 'Configuring the extinguishing card [
Alternatively, you can also assign the input type to the assigned element
directly at the relevant location in the 'Hardware tree'.
13. Highlight the 'Emergency hold' function in the 'Causes' zone.
14. Amend the customer text in the 'Overview' tab if necessary.
15. Configure the error behavior of the 'Emergency hold' function in the 'Details'
tab. NOTICE! Changes to this parameter can lead to error behavior which does
not correspond to the standard specifications. Only change this parameter if
the change complies with the standard specifications.
16. Assign the associated input, to which the 'Emergency hold' switches are
connected, on the extinguishing card to the 'Emergency hold' function with
'Assign'. This could be a 'Collective input', for example.
17. Highlight the assigned element and enter the required customer text in the
'Overview' tab.
18. Assign the input type to the assigned element in the 'Hardware' tab under
'Extinguishing input type'.
19. Optional: In the 'Causes' zone, create additional 'Causes' functions which are
required.
20. Optional: Configure the additionally created functions in the same way as the
'Causes' functions described above.
'Causes' functions – general
The 'Causes' functions described are templates with preset parameters. They can
be adjusted accordingly if necessary.
All 'Causes' functions must be assigned to the 'Assign dialog' with the
corresponding extinguishing card inputs, to which the relevant devices are
connected.