'Operation' task card
EVAC panel [NL]
13
298 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
Operation of the fire brigade key depot (FSD)
Figure 134: 'FSD', 'Hardware' detail editor
In the 'Hardware' detail editor, there are special settings for the fire brigade key
depot FSD if the checkbox in the 'Operated' field is checked:
●
'Release mode'. You can select when the fire brigade key depot is to be
unlocked:
– 'RT active/confirmed'
– 'Fire alarm or Gas alarm and RT active/confirmed'
– 'RT active/confirmed or RT active/unexpected'
●
'Released by Sabotage ALARM': If the checkmark is placed, the fire
department key depot is additionally unlocked by a sabotage alarm.
The sabotage alarm is triggered by a door contact built into the 'Station'. For
service purposes, the function can be switched off at the
Person Machine
Interface before the 'Station' is opened.
●
'Sabotage contact active upon 'FSD Sabotage'': If the checkmark is placed, the
specific output for notification of an intrusion panel is activated in the event of
an FSD sabotage message.
13.8 EVAC panel [NL]
The EVAC panel is an operating and indication unit for manual evacuation control,
Person Machine Interface of the control panel or remotely
connected via an RS485 interface. The EVAC panel consists of a master and up to
four slaves. Master and slave both have up to ten indicators for the evacuation
zones. Both the universal and two-stage evacuation control are suited to automatic
evacuation.
Creating 'Evac panel'
1. Select 'Operation' >
'Station' in the task card.
2. Create the 'Evac panel' element for the 'Station'. Link [
a
The 'Evac panel' element is created along with the 'Evac master' element.