'Operation' task card
EVAC panel [NL]
13
301 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
Properties of the 'Evac master' element – 'Details' tab
Figure 136: 'Evac master': Properties in the 'Details' tab
Property
Value
Description
'Buzzer silenced by FS720
operating terminal'
On/off
The property defines whether silencing the buzzer on
the FS720 operating terminal also silences the
buzzer of the EVAC panel.
'Access protection'
‒
The property defines the type of the access
protection for the EVAC panel.
The following options for the access protection can
be configured:
'No access protection'
●
All operating buttons on the EVAC panel are
always accessible.
'Key switch/PIN code on
FS720 operating terminal'
●
The access protection is provided by a key
switch or PIN code at the connected FS720
station.
Information: For this type of access protection,
the 'Access level of keys 'Start'/'Stop'' property
can be used to determine the access level that
the operating personnel require in order to use
the 'Start' and 'Stop' buttons. If this property is
not switched on, then the 'Start' and 'Stop'
buttons require access level 1 as standard.
'Key switch on Evac panel
protects 'IN/UIT' only'
●
The access protection is provided by a key
switch on the EVAC panel and only protects the
'IN/UIT' button
'Key switch on Evac panel
protects 'IN/UIT' +
'Start'/'Stop''
●
The access protection is provided by a key
switch on the EVAC panel and protects the
'IN/UIT', 'Start', and 'Stop' buttons.
'Enabled'
On/off
The checkbox determines whether the 'Access level
of keys 'Start'/'Stop'' property is switched on or not.
'Access level of keys
'Start'/'Stop''
Defines the access level required to execute the
functions of the 'Start' and 'Stop' keys.
Information: This property is only configurable if the
'Key switch/PIN code on FS720 operating terminal'
value has been set for the 'Access protection'
property.
Information: If this property is not switched on, then
the 'Start' and 'Stop' buttons require access level 1
as standard.
Creating 'Evac slave'
1. Select 'Operation' > 'Evac panel' in the task card.
2. Create the 'Evac slave' element for 'Evac panel'. Link [