Extinguishing
Configuring flooding zone control
16
369 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
12. Assign the associated output, to which the 'Sounder' is connected, on the
extinguishing card to the 'Sounder' function with 'Assign'. This is an
'Output/monitored' element.
13. Highlight the assigned element and enter the required customer text in the
'Overview' tab.
14. Configure the assigned element in the 'Hardware' tab.
15. Optional: Under the 'Effects' element, create additional 'Effects' functions which
are required.
16. Optional: Configure the additionally created functions in the same way as the
'Effects' functions described above.
'Effects' functions – general
The 'Effects' functions described are templates with preset parameters. They can
be adjusted accordingly if necessary.
All 'Effects' functions must be assigned to the 'Assign dialog' with the
corresponding extinguishing card outputs, to which the relevant devices are
connected.
With the exception of the 'Sounder' and 'Illuminated warning panel' functions, the
preset function type can be individually adjusted for all other 'Effects' functions. The
following function types are available:
●
'Actuator/valve'
●
'Exting. fire control'
●
'External equipment'
The function type selection affects which functions are switched off when the
corresponding isolation is triggered with the relevant button on the extinguishing
terminal.
The template of a specific element type always has a unique ID no. as part of the
'Template ID'. If two templates have the same ID number, then they are not the
same element type.
To uniquely identify an already created template, you can check the ID no. of the
template in the 'Details' tab under 'Template ID'.
In the template table, the ID no. and, if necessary, the element type for each
template is specified as the template names used here may differ from the names
in the Engineering Tool for localization-related reasons.