'Operation' task card
Integrating 'Cerberus PACE' system
13
310 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
6. Highlight the 'Visibility' element within the created 'Cerberus PACE' element.
7. Use 'Assign' to assign the visibility of the required parts of the fire detection
system to the 'Cerberus PACE' system. For example, this can be the station to
which the 'Cerberus PACE' system is connected.
Information: The 'Cerberus PACE' system only ever has visibility of the events
within the assigned zone of the fire detection system.
8. Optional: Highlight the assigned 'FC72x' station element under the 'Visibility'
element.
9. Optional: Adjust which events are visible for the 'Cerberus PACE' system in the
'Overview' tab. Presetting: The 'ALL event categories visible' property is
activated.