'Control' task card
Extinguishing standard interface SST [DE]
12
243 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
Creating an output for extinguishing actuation
An output of the input/output module is used to actuate the extinguishing process
via the extinguishing control system. The command for the extinguishing actuation
is give by detector zone(s) of the fire control panel.
Figure 70: 'New cause dialog, Assign dialog' window for assigning the cause for the extinguishing
actuation
Figure 71: 'New cause dialog, Assign dialog' window for assigning the effect for the extinguishing
actuation
effect of the extinguishing actuation, proceed as
follows:
1. Select the 'Control' task card.
2. Highlight the
'Station' in the tree view and create a
'Fire control group'
element and a 'Fire control' element below this.
3. Select 'Assign'.
a
The 'New cause dialog, Assign dialog' window opens.
4. Highlight 'Causes' and, in the 'New cause dialog' window, highlight ' ----All
autom. Fire ALARMS' in the 'Event' list.
5. Select the relevant automatic
zone(s) and click on 'Assign'.
a
'Causes' is assigned to the zone(s).
6. Highlight 'Fire control' and set the conditions for extinguishing activation in the
detail editor, 'Overview' button.
7. Highlight 'Effects' and, in the 'New effect dialog' window, highlight 'Output/NO
confirmation'.
8. Select the relevant 'Output' of input/output module FDCIO224 and click on
'Assign'.
a
'Effects' is assigned to the 'Output'.