Extinguishing
Configuring the extinguishing terminal
16
384 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
'Extinguishing terminal' – parameters in the 'Overview' tab
The table below describes the parameters in the 'Overview' tab for a 'Extinguishing
terminal' element:
Parameters
Values
Description
'Logout timeout'
Input field for time period
[Hr:min:sec]
Determines how long after the last press of
the button the operating terminal reverts to
the standard access level.
'Default access level'
'0'
'1'
'2.1'
'2.2'
The parameter determines the standard
access level for the 'Extinguishing
terminal'.
In extinguishing terminals with key
switches, the standard access level is
located in key position 'Off'.
'Access level PIN/key
switch'
The parameter determines the access level
for the 'Extinguishing terminal' if the PIN
has been entered or the key switch is in the
'On' position.
'Extinguishing terminal' – parameters in the 'Details' tab
The table below describes the parameters in the 'Details' tab for a 'Extinguishing
terminal' element:
Parameters
Values
Description
'Buzzer on communication
loss'
'Continuous'
The parameter determines which of the
sound characteristics are played by the
buzzer on the extinguishing terminal when
the communication connection between the
extinguishing terminal and relevant
extinguishing card is interrupted. The
following characteristics can be configured:
●
Continuous signal
'Intermittent, fast (0.25s on / 0.25s
off)'
●
Quick peeping sound
'Intermittent, slow (1.25s on / 0.75s
off)'
●
Slow peeping sound
'Single beep (2s)'
●
Single two-second-long peep
'Buzzer resound on
communication loss'
Input field for time period
[Hr:min:sec]
The parameter determines whether the
buzzer should play again as a reminder
when the communication connection
between the extinguishing terminal and
relevant extinguishing card is interrupted
and how long it should wait before playing
again.
The following configuration options are
available:
●
00:00:00 : The extinguishing terminal
does not switch the buzzer back on.
●
00:00:01...24:00:00 : The extinguishing
terminal switches the buzzer back on
after the selected time has elapsed.