Extinguishing
Configuring flooding zone control
16
378 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
'Effects' functions – 'Sounder' parameters in the 'Overview' tab
The table below describes the parameters in the 'Overview' tab for 'Effects'
functions of the 'Sounder' type.
Parameters
Values
Description
Parameters for the relevant
system states:
'Output mode
'Extinguishing pre-
activated''
'Output mode
'Extinguishing activated''
'Output mode 'Emergency
hold''
'Output mode
'Extinguishing released''
'Inactive: Off / active: Intermittent,
slow (1.25s/0.75s)'
Determines the signal characteristics of the
alarm sounder on the software side when it
is activated. The figures define the change
interval in which the alarm sounder sounds
and pauses again.
'xxx ([sound]s/[pause]s)'
Note: The bottom three signal
characteristics replicate the characteristics
of the existing extinguishing system XC10.
'Inactive: Off / active: Intermittent,
fast (0.25s/0.25s)'
'Inactive: Off / active: Intermittent,
pulse (0.25s/1.75s)'
'Inactive: Off / active: Intermittent,
slow (1s/4s)'
'Inactive: Off / active: Intermittent,
fast (1s/1s)'
'Inactive: Off / active: Intermittent,
pulse (4s/1s)'
'Always Off'
The alarm sounder is always switched off,
regardless of whether the effect function is
activated or not.
'Inactive: Off / active: On'
The alarm sounder issues a continuous
signal if the effect function is activated.
'Effects' functions – 'Illuminated warning panel' parameters in the
'Overview' tab
The table below describes the parameters in the 'Overview' tab for 'Effects'
functions of the 'Illuminated warning panel' type.
Parameters
Values
Description
Parameters for the relevant
system states:
'Output mode
'Extinguishing pre-
activated''
'Output mode
'Extinguishing activated''
'Output mode 'Emergency
hold''
'Output mode
'Extinguishing released''
'Output mode
'Mechanically blocked''
'Output mode 'Automatic
release blocked''
'Inactive: Off / active: Intermittent,
slow (1.25s/0.75s)'
Determines the signal characteristics of the
'Illuminated warning panel' if it is activated
via the effect function in a certain system
state. The figures define the change
interval in which the 'Illuminated warning
panel' lights up and pauses again.
'xxx ([light]s/[pause]s)'
Note: The bottom three signal
characteristics replicate the characteristics
of the existing extinguishing system XC10.
'Inactive: Off / active: Intermittent,
fast (0.25s/0.25s)'
'Inactive: Off / active: Intermittent,
pulse (0.25s/1.75s)'
'Inactive: Off / active: Intermittent,
slow (1s/4s)'
'Inactive: Off / active: Intermittent,
fast (1s/1s)'
'Inactive: Off / active: Intermittent,
pulse (4s/1s)'
'Always Off'
The 'Illuminated warning panel' is always
switched off, regardless of whether the
effect function is activated or not.
'Inactive: Off / active: On'
The 'Illuminated warning panel' lights up
permanently when the effect function is
activated.