Extinguishing
Basic configuration steps
16
345 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
16 Extinguishing
This chapter describes the configuration of the components for single-sector
extinguishing within an integrated FS720 fire detection and extinguishing system
with the engineering tool set FX7230.
16.1 Basic configuration steps
The configuration of the extinguishing components comprises the basic steps
described below. The detailed configuration processes are described in separate
chapters, which can be reached directly via a cross-reference.
The detailed configuration processes describe a pre-configuration of the
extinguishing components. Certain steps within the detailed configuration
processes are no longer necessary if the hardware was read in beforehand.
Single-sector extinguishing
w
A 'Station' element in which extinguishing can be integrated has already been
created and pre-configured. You will find more information on this in chapter
116].
w
The detector line for the flooding zone has already been created and pre-
configured.
w
All additional components required which do not directly belong to the
extinguishing function are already created and pre-configured.
1. Create an extinguishing card in 'Hardware tree' or read in and configure. Link
In this step, the extinguishing card and its inputs and outputs are configured for
the flooding zone of the extinguishing system.
2. Configure automatic activation for the flooding zone using the fire detector or
equivalent input signals. Link [
3. Create and configure the 'Extinguishing control group' element in the 'Control
The 'Extinguishing control group' element is a superordinate control element for
the flooding zone.
4. Create and configure a 'Extinguishing sector control' element for the flooding
zone within the 'Extinguishing control group'. Link [
An 'Extinguishing sector control' element contains all causes and effects of the
controls in the flooding zone.
5. Create and configure the 'Extinguishing reporting zone' element in the
'Detection tree'. Link [
In this step, the extinguishing reporting zone for one flooding zone is created
and configured. Within the assigned flooding zone, the extinguishing reporting
zone analyzes events, which indicate a pre-activated flooding zone or
extinguishing that has already been triggered.
6. Create and configure the 'Extinguishing terminal' element in the 'Operation
With a 'Extinguishing terminal' element, the buttons and lights on the
extinguishing terminal of the flooding zone are configured.