'Control' task card
Damper control group
12
236 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
12.6.3.2 Smoke dampers: Wiring and assignment
This chapter describes the wiring and assignment aspects based on the default
states of the damper controls [
Effects which can be
assigned
Input/Output of the FDCIO222/4
in Engineering Tool
Input on the
FDCIO222/4
Wired to contact/s...on the
damper actuator
Smoke extraction damper
output/supervised
21:Output
OUT A
M2
Damper output/NOT
supervised
22:Output
OUT B
M3
Input 'Damper inactive'
11:Input
IN 1
S1, S2
Input 'Damper active'
12:Input
IN 2
S4, S6
Contact position with 'Input 'Damper inactive'', smoke damper closed
1
Contacts S4 and S6 closed: Damper state closed
L
IN
E
-
L
IN
E
-
L
IN
E
+
L
IN
E
+
FDCIO222/4
21
22
23
24
14
13
12
11
IN1
IN2
IN3
IN4
OUT D OUT C
OUT
B
OUT
A
1
2
S1 S2 S3 S4 S5 S6
M
3
AC IN
DC IN -
AC IN
DC IN +
1