'Hardware' task card
'Station'
10
118 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
Configuring intervention concept
Figure 25: Detail editor with settings for the intervention concept
1. Select the 'Hardware' task card.
2. Highlight a
'Station' in the tree view.
3. Select the 'Intervention' tab in the detail editor and set the properties you want.
Immediate intervention
The following can be set for immediate intervention:
●
Separately for
'Manned operation' and
'Unmanned operation':
– 'Disabled'
– 'Delayed intervention'
– 'Global intervention only'
– 'Local intervention only'
●
Time t1 for (intervention) attendance check:
A new event must be acknowledged within this period, otherwise the
intervention concept switches to
global alarming.
● ↑
Alarming equipment:
'RT Fire', 'RT Fault', 'RT 1' - 'RT 8', 'Internal sounder'
Service intervention
The following can be set for service intervention:
●
Separately for 'Manned operation' and 'Unmanned operation':
– 'Disabled'
– 'Delayed intervention'
– 'Direct intervention'
●
Time for service intervention ts:
The cause of an event must be remedied within this time period, otherwise the
intervention concept activates the service intervention alarming equipment.
●
Alarming equipment:
'RT Fire', 'RT Fault', 'RT 1' - 'RT 8', 'Internal sounder'