Extinguishing
Configuring flooding zone control
16
370 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
Standard 'Effects' functions
The table below describes the 'Effects' functions, which the Engineering Tool
creates automatically in the 'Effects' zone with the creation of an 'Extinguishing
sector control' element. They are a fundamental part of the configuration for an
extinguishing system.
Designation
Description
'Actuator/valve main/res.
cyl. bank'
Element type: Function
Template ID: '14...'
Function for triggering the opening of the pneumatic shut-off valves on the main
or reserve extinguishing agent cylinders.
Information: The actuator for the valve can only ever be either opened or closed
with this function. Whether the actuator should be opened or closed depends on
the technical design of the opening mechanism. Furthermore, the function is only
intended for extinguishing systems with a central cylinder battery.
Information: If necessary, the element can be deleted and created again.
Activation state: ''Release actuator' phase'
Deactivation: After the time set under 'Activation duration' has elapsed
'Sounder'
Element type: Sounder
Template ID: '1...'
Function for activating the alarm sounder on the extinguishing terminal.
The function has special parameters which deviate from the standard in the
'Overview' tab. You will find information about the parameters in a separate
section in this chapter.
Information: The element cannot be deleted.