'Control' task card
Evac control group
12
218 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
12.4.3 Prioritized voice evac. control
The sounders FDS225 and FDS227 and the sounder base FDSB227 play
corresponding voice messages with an optional pre-notification tone instead of an
'Alert' tone or an 'Evac' tone. In addition to the phased voice evac. controls with
predefined priorities for the individual
control cause groups [link [
205]], these
devices can also be used to implement voice evac. controls with individually
prioritized cause groups. Individually prioritized voice evac. controls are configured
with the 'Prioritized voice evac control' element within a 'Evac control group'
element. For prioritized voice evac. controls, in addition to the predefined cause
groups, up to two completely freely configurable cause groups 'CUSTOM 1' and
'CUSTOM 2' can be created.
A 'Prioritized voice evac control' element has the following configuration options:
●
Assigning corresponding causes with the following cause groups for warning
and evacuating building zones:
– 'Causes EVAC FIRE (+DEGRADED MODE)'
– 'Causes EVAC EMERGENCY'
– 'Causes ALERT'
You will find more detailed information about the individual cause groups in a
separate table further down in this chapter.
●
Assigning corresponding causes with the following additional cause groups:
– 'Causes ALL-CLEAR'
– 'Causes TEST'
– 'Causes SCHOOL BELL'
– 'CUSTOM 1'
– 'CUSTOM 2'
You will find more detailed information about the individual cause groups in a
separate table further down in this chapter.
●
Configuring max. 7 cause groups under the 'Evac control group' element
●
Configuration of an audio sequence for each cause group
●
Configuration of an activation delay for each cause group
●
Configuration of the voice sounder which the system activates when the control
is activated