'Control' task card
Evac control group
12
222 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
Parameters
Value
Description
'DEACTIVATION allowed'
‒
The parameter determines whether the control can
be deactivated again when it has been automatically
activated by a cause.
The following options can be configured:
'NOT if activated
automatically by causes'
●
The control cannot be deactivated if it was
activated automatically by its causes. The control
can only be deactivated in the following
circumstances:
– The control has been activated by a manual
command on the
Person Machine
Interface.
– The control has been activated by a 'Fire
control' element.
– The control has been activated by a 'Time
control' element.
'Always'
●
Always
'Control test allowed'
On/off
The control can be set to the test state with a control
command on the Person Machine Interface when the
parameter is active.
'Prioritized voice evac control' – 'Causes' elements
The following table describes the configurable 'Causes' elements within a
'Prioritized voice evac control' element:
'Causes' element
Description
'Causes EVAC FIRE (+DEGRADED
MODE)'
Causes for triggering an optional 'Pre-announce tone' tone and a pre-
configured voice message to evacuate building zones due to a fire
alarm.
The 'Pre-announce tone' tone and configured voice message are also
played when a fire alarm has been activated in
degraded mode.
'Causes EVAC EMERGENCY'
Causes for triggering an optional 'Pre-announce tone' tone and a pre-
configured voice message to evacuate building zones due to an
emergency in the building.
This includes all causes for triggering an evacuation apart from those
triggered by a fire alarm.
'Causes ALERT'
Causes for triggering an optional 'Pre-announce tone' tone and a pre-
configured voice message to warn people in various building zones
about a dangerous situation.
'Causes ALL-CLEAR'
Causes for triggering an optional 'Pre-announce tone' tone and a pre-
configured voice message to override an existing evacuation or alarm
message.
'Causes SCHOOL BELL'
Causes for triggering a school bell.
'Causes TEST'
Causes for triggering a pre-configured test voice message.
'Causes CUSTOM 1'
'Causes CUSTOM 2'
Up to two additional user-defined cause groups can be created for
'Prioritized voice evac control' elements. A user-defined cause group
contains freely configurable voice messages in the 'Audio sequence'
tab. You will find more information on this in chapter 'Configuring an