'Operation' task card
Fire brigade periphery [DE]
13
294 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
Visibility configuration
visibility that the event printer logs is defined in the 'Visibility' element.
The following selection is available:
●
'Site': Visibility for the entire
site.
●
'Site without areas': Visibility for all events from the 'Hardware tree' of the site.
●
'Station': Visibility for one 'Station' within the site, with all
areas in this
'Station'
●
'Station without areas': Visibility for all events from the 'Hardware tree' of the
'Station'.
●
'Area': Visibility on an area within a control panel
Figure 129: 'Assign dialog' window for assigning the visibility
To configure the visibility, proceed as follows:
1. Select the 'Operation' task card.
2. In the tree view, open 'Built-in printer' or 'External printer' and highlight
'Visibility'.
3. Open the 'Assign dialog' window.
a
'Visibility' list and the 'Hardware tree' or
detection tree are displayed.
4. Select the site, station, or
area and click on 'Assign' (you can assign the
visibility to several elements).
a
'Visibility' is assigned to the corresponding element.
13.7 Fire brigade periphery [DE]
The fire brigade periphery comprises the following devices:
●
FBF: Fire brigade operating panel
●
FSD: Fire brigade key depot
●
FAT: Fire brigade indication panel
●
FAT with FBF: Fire brigade indication panel with fire brigade operating panel
●
FSE: Releasing element link [
The devices are connected as follows:
●
FSD is assigned to the fire brigade periphery module FCI2001.
●
FBF can either be connected via the fire brigade periphery module FCI2001 or
an RS485 interface.
●
FAT and FAT with FBF are connected to the
'Station' via an RS485 serial
interface.
To configure the devices, the logical element must be created in the 'Operation'
task card and assigned to the corresponding hardware element.