'Operation' task card
Fire brigade periphery [DE]
13
297 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
●
Fire brigade indication panel FAT:
– Visibility:
'Site': visibility on the entire site
'Site without areas': Visibility for all events from the Hardware tree of the
site.
'Station': Visibility for one 'Station' within the site, with all areas in this
'Station'.
'Station without areas': Visibility for all events from the 'Hardware tree' of
the 'Station'.
'Area': Visibility on an area within a control panel
●
Fire brigade indication panel FAT with fire brigade operating panel FBF:
– Same visibilities as FAT and/or FBF
The visibilities for 'Site', 'Area' and 'Station' can be restricted further so that, for
example, only the alarm and fault event categories are displayed instead of all
events for an area.
Figure 132: Configuring visibility of logical elements
To configure the visibility, proceed as follows:
1. Select the 'Operation' task card.
2. In the tree view, open the element to be configured, e.g. 'FBF'.
3. Highlight the control 'Visible Extinguishing zones,' for example.
4. Open the 'Assign dialog' window.
a
'Visible Extinguishing zones' is highlighted.
5. Select the corresponding element in the
control tree and click on 'Assign'.
a
'Visible Extinguishing zones' is assigned to the selected element.
Figure 133: 'FBF' detail editor for selecting certain event categories
One or more event categories can be selected in the detail editor of the assigned
elements.