'Control' task card
Sounder line via input/output module FDCIO223
12
249 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
Configuring 'Sounder'
Figure 78: 'Control' task card with 'Hardware' detail editor
The 'Sounder' configuration is displayed in the detail editor of the 'Control' task
card, provided that the following conditions are met:
●
'Sounder' is assigned to the control
effect.
●
'Sounder' is highlighted in the tree view.
In the detail editor the following configurations are possible:
●
'ALERT tone', 'EVAC tone', and 'Sounder volume' can be set under 'Hardware'.
●
For the 'Sounder beacon', 'Beacon activation' can also be configured under
'Hardware.
●
Under 'Overview', a time limit can also be set for 'Manned operation' and
'Unmanned operation' separately.
The settings for 'Sounder' can also be viewed in the detail editor of the 'Hardware'
task card, under 'Overview' and 'Control'.
12.10 Sounder line via input/output module FDCIO223
You can use the two inputs/outputs of the input/output module FDCIO223 for the
connection of 'Sounder' lines.
You can assign a 'Sounder' line as an
effect for the following controls:
●
'Internal sounder control'
●
'External sounder control'
●
'Universal sounder evac control'
●
'Phased sounder evac control'
Assigning the 'Sounder' line
Figure 79: Assigning sounder line
1. Select the 'Control' task card.
2. In the tree view, open the
'Station' and then one of the following controls:
– 'Alarming control group' > 'Internal sounder control' or 'External sounder
control'
– 'Evac control group' > 'Universal sounder evac control' or 'Phased sounder
evac control'
3. Highlight the 'Effects' element.