'Control' task card
Damper control group
12
234 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
Description of the effect elements
The following effects are pre-configured:
●
'Fire damper control'
– 'Fire damper output/supervised': Control of the damper actuator motor for
opening or closing the damper. The inputs for monitoring the damper state
are located under this output.
– 'Damper output/NOT supervised': The wiring for the energy supply can be
routed via this output.
●
'Smoke extraction control'
– 'Smoke extraction damper output/supervised': Counterclockwise control of
the damper actuator motor for opening the damper. The inputs for
monitoring the damper state are located under this output.
– 'Damper output/NOT supervised': Clockwise control of the damper actuator
motor for closing the damper. This output is inverted by default because the
normal condition of the damper is 'closed', i.e., when the control is in the
inactive state, the output contact is closed/active.
12.6.3.1 Fire dampers: Wiring and assignment
This chapter describes the wiring and assignment aspects based on the default
states of the damper controls [
Effects which can be
assigned
Input/Output of the FDCIO222/4
in Engineering Tool
Contact on the
FDCIO222/4
Wired to contact/s...on the
damper actuator
Fire damper
output/supervised
21:Output
OUT A
M1
Damper output/NOT
supervised
22:Output
OUT B
M2
Input 'Damper inactive'
11:Input
IN 1
S4 and S6
Input 'Damper active'
12:Input
IN 2
S1 and S2