'Control' task card
Evac control group
12
203 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
'Phased sounder evac control' – parameters in the 'Details' tab
Parameters
Value
Description
'Accept commands
'Sounders ON/OFF'' from
FBF'
On/off
Acoustic sounders connected to the control can be
switched off at any time using the corresponding
button on the fire brigade operating panel (FBF)
when the parameter is activated.
'OFF allowed'
‒
The parameter defines whether the control can be
switched off.
The following options can be configured:
'Never'
●
Never
'NOT if activated
automatically by causes'
●
The control cannot be switched off if it was
activated automatically by its causes. The control
can only be switched off in the following
circumstances:
– The control is in an idle state.
– The control has been activated by a manual
command on the
Person Machine
Interface.
– The control has been activated by a 'Fire
control' element.
– The control has been activated by a 'Time
control' element.
'Always'
●
Always
'DEACTIVATION allowed'
‒
The parameter determines whether the control can
be deactivated again when it has been automatically
activated by a cause.
The following options can be configured:
'NOT if activated
automatically by causes'
●
The control cannot be deactivated if it was
activated automatically by its causes. The control
can only be deactivated in the following
circumstances:
– The control has been activated by a manual
command on the
Person Machine
Interface.
– The control has been activated by a 'Fire
control' element.
– The control has been activated by a 'Time
control' element.
'Always'
●
Always
'Control test allowed'
On/off
The control can be set to the test state with a control
command on the Person Machine Interface when the
parameter is active.