'Control' task card
Evac control group
12
225 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
'Prioritized voice evac control' – 'Effects' assignments – parameters in
the 'Overview' tab
The following table describes possible parameters in the 'Overview' tab for 'Effects'
assignments:
Parameters
Values
Description
'Enabled'
On/off
Activates or deactivates the 'Activation timeout
'manned'' parameter.
'Activation timeout
'manned''
Input field for time period
[hh:mm:ss]
Adjustment range: 0...100
min
Increments: 1 sec
The parameter specifies the time that needs to
elapse in 'Manned' operation before the assigned
alarm device is automatically deactivated again.
'Enabled'
On/off
Activates or deactivates the 'Activation timeout
'unmanned'' parameter.
'Activation timeout
'unmanned''
Input field for time period
[hh:mm:ss]
Adjustment range: 0...100
min
Increments: 1 sec
The parameter specifies the time that needs to
elapse in 'Unmanned' operation before the assigned
alarm device is automatically deactivated again.
See also
2
2
Configuring an audio sequence [
2