'Control' task card
Evac control group
12
196 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
Parameters
Values
Description
'Enabled'
On/off
The parameter determines a defined time period.
Once this period has elapsed, the control is
automatically deactivated again, even if at least one
activation condition is still met.
The time period starts to run as soon as the system
activates the control.
Note: The 'Activation timeout' parameter and the
'Deactivation timeout' parameter cannot be activated
at the same time. The configuration tool displays an
error when both parameters are activated at the
same time.
'Activation timeout'
Input field for time period
[hh:mm:ss]
Adjustment range: 0...30
sec
Increments: 1 sec
'Enabled'
On/off
The parameter determines a defined time period.
Once this period has elapsed, the control is
automatically activated again, even if no activation
condition is met.
The time period starts to run as soon as the system
deactivates the control.
Note: The 'Activation timeout' parameter and the
'Deactivation timeout' parameter cannot be activated
at the same time. The configuration tool displays an
error when both parameters are activated at the
same time.
'Deactivation timeout'
Input field for time period
[hh:mm:ss]
Adjustment range: 0...30
sec
Increments: 1 sec
'Universal sounder evac control' – parameters in the 'Details' tab
Parameters
Value
Description
'Accept commands
'Sounders ON/OFF'' from
FBF'
On/off
Acoustic sounders connected to the control can be
switched off at any time using the corresponding
button on the fire brigade operating panel (FBF)
when the parameter is activated.
'OFF allowed'
‒
The parameter defines whether the control can be
switched off.
The following options can be configured:
'Never'
●
Never
'NOT if activated
automatically by causes'
●
The control cannot be switched off if it was
activated automatically by its causes. The control
can only be switched off in the following
circumstances:
– The control is in an idle state.
– The control has been activated by a manual
command on the
Person Machine
Interface.
– The control has been activated by a 'Fire
control' element.
– The control has been activated by a 'Time
control' element.
'Always'
●
Always