'Operation' task card
Floor repeater terminal FT2010 and floor repeater display FT2011
13
284 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
13.4.2 Visibility
Display
The 'Visibility' element can be used to determine which events can be shown in the
floor repeater terminal (FRT) and the
floor repeater display
(FRD).
The following selection is available:
● ↑
Visibility for the entire 'Site'
●
'Site without areas': Visibility for all events from the Hardware tree of the'Site'
● ↑
'Station': Visibility for a Station within the Site, with all areas in this Station
●
'Station without areas': Visibility for all events from the 'Hardware tree' of the
'Station'
● ↑
'Area': Visibility for one 'Area' within a control panel
● ↑
'Section': Visibility for one 'Section' within a control panel
● ↑
'Zone': Visibility for one 'Zone' within a control panel
This can be restricted further, so that for example only the alarm and fault event
categories are displayed instead of all events of an area.
Assigning 'Visibility'
1. Select the 'Operation' task card.
2. Open
'Station' > 'FRT/FRD core' > 'FRT configuration group' or 'FRD
configuration group' in the tree view.
3. Highlight 'Visibility'.
4. Open the 'Assign dialog' window.
a
The event categories of 'Visibility' are displayed.
5. Select the event category and the corresponding 'Station', 'Area', 'Section' or
'Zone' element, and click on 'Assign'.
a
'Visibility' is assigned to the element.
Selecting element categories
One or more event categories can be selected in the detail editor of the assigned
elements.
Figure 115: 'Section' detail editor for selecting specific event categories