Extinguishing
Configuring flooding zone control
16
359 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
16.5.1 Causes functions
Causes for activating or deactivating controls are configured with 'Causes'
functions. The causes are assigned to the corresponding inputs on the
extinguishing card. A 'Causes' function can be assigned up to eight inputs which
trigger the respective 'Causes' function. The assigned inputs are logically
connected to each other with a simple OR assignment. Each input triggers the
function independently of the other inputs.
Creating, assigning, and configuring 'Causes' functions
The sequence only contains the necessary configuration steps. You will find
information about the elements that can be assigned or created, as well as the
parameters, in separate sections further down in this chapter.
w
An 'Extinguishing sector control' element is created under the 'Extinguishing
control group' element.
1. Highlight the 'Automatic release' function in the 'Causes' zone.
2. Amend the customer text in the 'Overview' tab if necessary.
3. Assign one or more of the previously configured 'Zone' elements as a cause to
the 'Automatic release' function using 'Assign'.
4. Highlight the 'Automatic release' function in the 'Causes' zone again.
5. In the 'Overview' tab, configure how the 'Automatic release' function should
evaluate the assigned activation zones in order to activate or trigger the
flooding zone.
6. Highlight the 'Manual release' function in the 'Causes' zone.
7. Amend the customer text in the 'Overview' tab if necessary.
8. Configure the error behavior of the 'Manual release' function in the 'Details' tab.
NOTICE! Changes to this parameter can lead to error behavior which does not
correspond to the standard specifications. Only change this parameter if the
change complies with the standard specifications.