'Hardware' task card
C-NET detector line
10
132 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
'Collective line type'
This setting specifies which type of
collective detector line is connected.
'Coll. line: alarm response / fault delay'
This setting specifies the alarm reaction time and the fault delay time of the
collective detector line. The alarm reaction time refers to the device's internal
alarm verification. Values in brackets are outside the authorized range.
'Input inverted'
This setting specifies whether the input is inverted.
●
Checkbox activated: Input is active when signal is changing from HIGH to
LOW.
●
Checkbox deactivated: Input is active when signal is changing from LOW to
HIGH.
'Input monitoring':
This setting specifies the monitoring of the input:
●
Monitoring for open line
●
Monitoring for short circuit and open line
●
No monitoring
'ALERT mode'
This setting defines the behavior of the output signal in the 'Alert' mode for the
active or inactive status of the logic.
'EVAC/output mode'
●
Use as sounder line: The setting defines the behavior of the output signal in the
'Evac' mode for the active or inactive status of the logic.
●
If used as a monitored output: This setting defines the behavior of the output
signal in the active or inactive status of the logic.
'Sounder line/output: fault delay'
This setting specifies the delay time for the transmission of faults of the sounder
line or of the output, respectively. Values in brackets are outside the authorized
range.
'Sounder line/output: load resistor'
This setting specifies the load resistance for the monitoring of the sounder line or of
the output, respectively.
'Output fail safe position'
This setting specifies the position of the output if the communication between
device and line interface is disrupted or if the line voltage fails.