Extinguishing
Configuring the forwarding of the extinguishing released state
16
391 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
'Local event' elements – parameters in the 'Overview' tab
The table below describes the parameters in the 'Overview' tab for a 'Local event'
element:
Parameters
Value
Description
'Colour'
'Red'
Lighting color of the LED when
activated
'Yellow'
'Green'
'Blue'
'White'
'Purple'
'LED mode'
'Off'
Lighting mode of the LED when
activated
'Intermittent, fast (0.25s/0.25s)'
'Intermittent, slow (1.25s/0.75s)'
'On '
'Priority'
'01 (highest)'
Priority of the cause compared with
other causes which are assigned to the
same LED.
'2'
'3'
See also
2
2
Configuring inputs and outputs [
16.8 Configuring the forwarding of the extinguishing
released state
General
The EN 12094-1 standard stipulates that the 'Released' state of a flooding zone
must be transmitted to an output for further use.
This requirement is implemented with the aid of universal controllers which transmit
the 'Released' extinguishing state of a flooding zone to any output of the fire control
panel with integrated extinguishing.
The configuration comprises three basic steps:
1. Creation and configuration of a 'Fire control' element for recording the
'Released' state of the 'Extinguishing reporting zone' element of a flooding zone
and forwarding to any output.
2. Creation and configuration of a 'Fire control' element for transmitting a potential
'Isolation' state of the first 'Fire control' element to the flooding zone control.
3. Creation and configuration of an 'Auxiliary function off' element for recording
and publishing the 'Isolation' state on the flooding zone control side.