'Operation' task card
Floor repeater terminal FT2010 and floor repeater display FT2011
13
283 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
4. Select 'Standard visibility'.
5. Select 'Assign'.
6. In the 'Assign' window, select the 'Station' on which you want to set 'Visibility'
for smartphones and confirm your choice by clicking 'Assign'.
7. Go to the tree view and select the assigned 'Station'. Then select the
'Overview' tab.
8. Activate the 'ALL event categories visible' option.
a
'Visibility' for smartphones has now been specified.
a
All 'Event categories of the 'Station' are visible for smartphones.
Figure 114: Configuring
visibility
13.4 Floor repeater terminal FT2010 and floor repeater
display FT2011
Floor repeater terminal (FRT)
The following can be configured for the
floor repeater terminal:
● ↑
Visibility
●
Causes for the activation of the LEDs
●
Six keys
Floor repeater display (FRD)
The following can be configured for the
floor repeater display:
●
Visibility
●
Causes for the activation of a LED
13.4.1 FT2010/FT2011 core and configuration groups
In order to configure the floor repeater terminal (FRT) or floor repeater display
(FRD), in the task card 'Operation', for each C-NET line card (onboard/FCL2001)
where floor repeater terminals or displays are connected to the C-NET detector
line, an element 'FRT/FRD core' is created. 'FRT configuration group' elements can
be created for the floor repeater terminals and 'FRD configuration group' for the
floor repeater displays. Each of these elements can be assigned to up to eight
'FRT' (FT2010) or 'FRD' (FT2011).
It is currently also possible to assign 'FRT' or 'FRD' which are connected to
another C-NET line card (onboard/FCL2001).
Only assign channels that are connected to the C-NET line card
(onboard/FCL2001) assigned to the 'FRT/FRD core' element.