Extinguishing
Configuring an extinguishing reporting zone
16
379 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
'Effects' functions – parameters in the 'Details' tab
The error handling in the 'Details' tab only works for effects which are connected
to the extinguishing card directly. The error behavior of effects, which are not
connected to the extinguishing card directly, must be configured in a special
'Causes' function, such as 'Fault -> 'Block autom. release''.
Parameters
Values
Description
'Fault behaviour [EN
12094-1 requirements: see
tooltip]'
NOTICE! Changes to this
parameter can lead to error
behavior which does not
correspond to the standard
specifications. Only
change this parameter if
the change complies with
the standard specifications.
'Block autom.+man. release'
In the event of an error, the site switches
automatically into the 'Block
aumanual release' operation mode
at the allocated output of the 'Effects'
function.
'Block autom. release'
In the event of an error, the site switches
automatically into the 'Block automatic
release' operation mode at the allocated
output of the 'Effects' function.
'Activate but don't release'
In the event of an error, the site activates
an extinguishing process at the allocated
output of the 'Causes' function but does not
trigger extinguishing.
'No blocking'
In the event of an error, the site does not
block the automatic or manual activation of
extinguishing at the allocated output of the
'Effects' function.
See also
2
Configuring the extinguishing card [
16.6 Configuring an extinguishing reporting zone
An 'Extinguishing reporting zone' element monitors whether extinguishing has been
triggered in the flooding zone. It triggers an alarm as soon as the extinguishing
control in the flooding zone transmits the output signal for a triggered extinguishing
process.
Furthermore, the extinguishing reporting zone consolidates all isolations and errors
within the flooding zone and publishes corresponding reports for both categories.
The 'Extinguishing reporting zone' element has two different templates that differ in
the event category with which an extinguishing trigger is reported:
●
'Reporting 'pre-alarm'': ' ----Pre-ALARM, extinguishing released'
The alarm process with this event category is compliant with standards.
●
'Reporting 'alarm'': ' ------Exting. discharged (Aut. Fire AL.)'
The alarm process with this event category is not compliant with standards.
If the system issues triggered extinguishing with the 'Reporting 'alarm'' template,
the operating personnel can only reset the alarm at the Person Machine Interface
of the station. It is not possible to perform a reset at the relevant extinguishing
terminal.
If the system issues triggered extinguishing with the 'Reporting 'pre-alarm''
template, the operating personnel can also reset the alarm at the relevant
extinguishing terminal.