L-VIS User Manual
303
LOYTEC
Version 6.2
LOYTEC electronics GmbH
configuration server to form the IP-852 channel list. The port can be changed and
disabled. This port is disabled by default (as long as the IP-852 configuration
server is not enabled).
1630 udp/tcp: Only LVIS-3E1xx models running on the FT-10 interface (IP852
disabled). This port is used by the CEA-709 RNI and for the remote LPA. The
port can be changed and disabled.
5900 tcp: This port is opened by the VNC server, if enabled in the project
settings. The port can be changed and disabled. This port is disabled by default.
47808 udp: This is the data exchange port for BACnet/IP. It is required for the
primary function of the device only on BACnet models running on BACnet/IP
(not MS/TP). The port can be changed and disabled.
15.9.3 Services
Possibly required services:
LVIS-3E1xx with IP-852 interface enabled, as well as any other device using
global connections: CEA-852 (LON over IP). This service is in accordance with
the standard ANSI/CEA-852-B.
LVIS-ME2xx with BACnet/IP interface enabled: BACnet/IP. This service is in
accordance with the standard ANSI/ASHRAE 135-2010.
Optional services not necessary for the primary product function:
HTTP: Web server. It provides a Web-based configuration UI. The Web UI can
be disabled after setting up the device.
OPC XML-DA: This Web service provides access to data points over the OPC
XML-DA standard. It is available only when the HTTP server is enabled.
SSH: Secure shell server, available on LVIS-3E11x/ME21x devices only. It can
be used for a secure connection to the device by the configuration software for
configuration and firmware upgrade. On devices that do not have SSH,
Telnet/FTP must be used instead.
FTP and Telnet: The FTP and Telnet servers are used for connection to the
device by the configuration software for configuration, firmware upgrade, and
access to the log file. On devices without SSH server, these services must be
enabled during device configuration.
VNC: The VNC server can be used for remote access to the LCD display on
devices where it is enabled in the project settings. The service is disabled by
default.
RNI: This service provides the remote network interface (RNI) function on
LVIS-3E1xx devices running on the FT-10 interface. It is also used by the remote
LPA feature. If these features are not needed the service can be disabled.
15.9.4 Logging and Auditing
The device contains a log file which can be read out via FTP, the configuration software, or
the Web server. This log contains information about when the device started and when
crucial communication errors occur. Other events such as user log-on are logged in a
separate operating system log, which is available on LVIS-3E11x/ME21x devices via the
web UI.
Events recorded in the system log:
Time of the last power-on reset of the device.
Time and version of the last firmware upgrade.