Figure 27: Create New Alarm Server dialog box.
4.
For alarm transitions, you may define which ones require acknowledgement, and at
which priority they are reported.
5.
You may attach data points for storing alarm counters. These will be linked using the
respective property relations (see Section 10.1.10).
6.
When you create a generic alarm server, you may add technology alarm servers that
shall be reported to. Click on
and choose one alarm server of each technology. If
they don’t exist, you need to create them under the technology port folders.
7.
Click
Create
. The alarm server appears now in the data point list view.
8.
For a BACnet technology alarm server, edit the instance number of the Notification
Class object to fit your needs.
10.11.2 Create an Alarm Condition
To generate alarms from data points, intrinsic reporting is used. For each data point an
alarm condition must be defined. This condition employs an intrinsic algorithm to generate
alarms based on the data point’s value or by evaluating a feedback value. Depending on the
data point type (analog, binary, multi-state), different conditions are defined. The alarm is
reported to the attached alarm server.
To Create an Intrinsic Alarm Condition
1.
Select a data point.
2.
Right-click and select
Create Alarm Condition…
from the context menu.