L-VIS User Manual
246
LOYTEC
Version 6.2
LOYTEC electronics GmbH
2.
Right-click on the data point and select
Add/Remove BACnet properties …
from the
context menu. The dialog appears as shown below.
Figure 35: Dialog for adding/removing BACnet properties.
3.
Check the additional properties. Checking the
Read
box will add an input data point,
checking the
R/W
box will add a value data point.
4.
Click
Close
. The selected data point can now be expanded with the plus icon and show
its additional properties as sub-data points.
5.
To remove properties perform the same steps and uncheck the corresponding check-
boxes. Alternatively, select the property (or more) and press the
Delete
key.
10.16.3.2 Read the Active Priority
In BACnet objects that possess a priority array the effective value depends on the used
write priority slots. A special data point on the device can be added that allows reading out
the active priority of such an object, giving a value between 1 and 16.
To Read the Active Priority of a Local Object
1.
Select the BACnet server object for adding properties.
2.
Right-click on the data point and select
Add/Remove BACnet properties …
from the
context menu. The dialog for mapping BACnet properties to data points appears.
3.
For
the Present_Value
select the additional box Active Priority.
To Read the Active Priority of a Feedback Value
1.
Select a write client mapping.
2.
Right-click on the data point and select
Create Priority Feedback Point
from the
context menu.