C.7.1 LOGICAL NODES TABLE
The UR-series of relays supports IEC 61850 logical nodes as indicated in the following table. Note that the actual instantia-
tion of each logical node is determined by the product order code. For example. the logical node “PDIS” (distance protec-
tion) is available only in the D60 Line Distance Relay.
Table C–1: IEC 61850 LOGICAL NODES (Sheet 1 of 3)
NODES
UR-FAMILY
L: SYSTEM LOGICAL NODES
LPHD
: Physical device information
Yes
LLN0
: Logical node zero
Yes
P: LOGICAL NODES FOR PROTECTION FUNCTIONS
PDIF
: Differential
Yes
PDIR
: Direction comparison
---
PDIS
: Distance
Yes
PDOP
: Directional overpower
---
PDUP
: Directional underpower
---
PFRC
: Rate of change of frequency
---
PHAR
: Harmonic restraint
---
PHIZ
: Ground detector
---
PIOC
: Instantaneous overcurrent
Yes
PMRI
Motor restart inhibition
---
PMSS
: Motor starting time supervision
---
POPF
: Over power factor
---
PPAM
: Phase angle measuring
---
PSCH
: Protection scheme
---
PSDE
: Sensitive directional earth fault
---
PTEF
: Transient earth fault
---
PTOC
: Time overcurrent
Yes
PTOF
: Overfrequency
---
PTOV
: Overvoltage
Yes
PTRC
: Protection trip conditioning
Yes
PTTR
: Thermal overload
Yes
PTUC
: Undercurrent
---
PTUV
: Undervoltage
Yes
PUPF
: Underpower factor
---
PTUF
: Underfrequency
---
PVOC
: Voltage controlled time overcurrent
---
PVPH
: Volts per Hz
---
PZSU
: Zero speed or underspeed
---
R: LOGICAL NODES FOR PROTECTION RELATED FUNCTIONS
RDRE
: Disturbance recorder function
---
RADR
: Disturbance recorder channel analogue
---
RBDR
: Disturbance recorder channel binary
---
RDRS
: Disturbance record handling
---
RBRF
: Breaker failure
Yes
RDIR
: Directional element
---
RFLO
: Fault locator
Yes
RPSB
: Power swing detection/blocking
Yes
RREC
: Autoreclosing
Yes
Содержание UR Series C70
Страница 2: ......
Страница 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C70 Capacitor Bank Protection and Control System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 124: ...4 30 C70 Capacitor Bank Protection and Control System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 344: ...5 220 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 396: ...8 18 C70 Capacitor Bank Protection and Control System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 414: ...9 18 C70 Capacitor Bank Protection and Control System GE Multilin 9 1 OVERVIEW 9 THEORY OF OPERATION 9 ...
Страница 436: ...10 22 C70 Capacitor Bank Protection and Control System GE Multilin 10 4 SETTING EXAMPLE 10 APPLICATION OF SETTINGS 10 ...
Страница 547: ...GE Multilin C70 Capacitor Bank Protection and Control System B 79 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 548: ...B 80 C70 Capacitor Bank Protection and Control System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 586: ...D 10 C70 Capacitor Bank Protection and Control System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Страница 598: ...E 12 C70 Capacitor Bank Protection and Control System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...