GE Multilin
C70 Capacitor Bank Protection and Control System
5-37
5 SETTINGS
5.2 PRODUCT SETUP
5
5.2.7 USER-PROGRAMMABLE FAULT REPORTS
PATH: SETTINGS
Ö
PRODUCT SETUP
ÖØ
USER-PROGRAMMABLE FAULT REPORT
Ö
USER-PROGRAMMABLE FAULT REPORT 1(2)
When enabled, this function monitors the pre-fault trigger. The pre-fault data are stored in the memory for prospective cre-
ation of the fault report on the rising edge of the pre-fault trigger. The element waits for the fault trigger as long as the pre-
fault trigger is asserted, but not shorter than 1 second. When the fault trigger occurs, the fault data is stored and the com-
plete report is created. If the fault trigger does not occur within 1 second after the pre-fault trigger drops out, the element
resets and no record is created.
The user programmable record contains the following information: the user-programmed relay name, detailed firmware
revision (5.7x, for example) and relay model (C70), the date and time of trigger, the name of pre-fault trigger (a specific
FlexLogic™ operand), the name of fault trigger (a specific FlexLogic™ operand), the active setting group at pre-fault trig-
ger, the active setting group at fault trigger, pre-fault values of all programmed analog channels (one cycle before pre-fault
trigger), and fault values of all programmed analog channels (at the fault trigger).
Each fault report is stored as a file to a maximum capacity of ten files. An eleventh trigger overwrites the oldest file. The
EnerVista UR Setup software is required to view all captured data. A
FAULT RPT TRIG
event is automatically created when
the report is triggered.
The relay includes two user-programmable fault reports to enable capture of two types of trips (for example, trip from ther-
mal protection with the report configured to include temperatures, and short-circuit trip with the report configured to include
voltages and currents). Both reports feed the same report file queue.
The last record is available as individual data items via communications protocols.
•
PRE-FAULT 1 TRIGGER:
Specifies the FlexLogic™ operand to capture the pre-fault data. The rising edge of this
operand stores one cycle-old data for subsequent reporting. The element waits for the fault trigger to actually create a
record as long as the operand selected as
PRE-FAULT 1 TRIGGER
is “On”. If the operand remains “Off” for 1 second, the
element resets and no record is created.
•
FAULT 1 TRIGGER:
Specifies the FlexLogic™ operand to capture the fault data. The rising edge of this operand
stores the data as fault data and results in a new report. The trigger (not the pre-fault trigger) controls the date and time
of the report.
•
FAULT REPORT 1 #1
to
FAULT REPORT 1 #32:
These settings specify an actual value such as voltage or current
magnitude, true RMS, phase angle, frequency, temperature, etc., to be stored should the report be created. Up to 32
channels can be configured. Two reports are configurable to cope with variety of trip conditions and items of interest.
USER-PROGRAMMABLE
FAULT REPORT 1
FAULT REPORT 1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
PRE-FAULT 1 TRIGGER:
Off
Range: FlexLogic™ operand
MESSAGE
FAULT 1 TRIGGER:
Off
Range: FlexLogic™ operand
MESSAGE
FAULT REPORT 1 #1:
Off
Range: Off, any actual value analog parameter
MESSAGE
FAULT REPORT 1 #2:
Off
Range: Off, any actual value analog parameter
↓
MESSAGE
FAULT REPORT 1 #32:
Off
Range: Off, any actual value analog parameter
Содержание UR Series C70
Страница 2: ......
Страница 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C70 Capacitor Bank Protection and Control System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 124: ...4 30 C70 Capacitor Bank Protection and Control System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 344: ...5 220 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 396: ...8 18 C70 Capacitor Bank Protection and Control System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 414: ...9 18 C70 Capacitor Bank Protection and Control System GE Multilin 9 1 OVERVIEW 9 THEORY OF OPERATION 9 ...
Страница 436: ...10 22 C70 Capacitor Bank Protection and Control System GE Multilin 10 4 SETTING EXAMPLE 10 APPLICATION OF SETTINGS 10 ...
Страница 547: ...GE Multilin C70 Capacitor Bank Protection and Control System B 79 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 548: ...B 80 C70 Capacitor Bank Protection and Control System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 586: ...D 10 C70 Capacitor Bank Protection and Control System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Страница 598: ...E 12 C70 Capacitor Bank Protection and Control System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...