B-10
C70 Capacitor Bank Protection and Control System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
User Displays Actuals (Read Only)
1080
Formatted user-definable displays (16 items)
---
---
---
F200
(none)
Modbus User Map Actuals (Read Only)
1200
User Map Values (256 items)
0 to 65535
---
1
F001
0
Element Targets (Read Only)
14C0
Target Sequence
0 to 65535
---
1
F001
0
14C1
Number of Targets
0 to 65535
---
1
F001
0
Element Targets (Read/Write)
14C2
Target to Read
0 to 65535
---
1
F001
0
Element Targets (Read Only)
14C3
Target Message
---
---
---
F200
“.”
Digital Input/Output States (Read Only)
1500
Contact Input States (6 items)
0 to 65535
---
1
F500
0
1508
Virtual Input States (8 items)
0 to 65535
---
1
F500
0
1510
Contact Output States (4 items)
0 to 65535
---
1
F500
0
1518
Contact Output Current States (4 items)
0 to 65535
---
1
F500
0
1520
Contact Output Voltage States (4 items)
0 to 65535
---
1
F500
0
1528
Virtual Output States (6 items)
0 to 65535
---
1
F500
0
1530
Contact Output Detectors (4 items)
0 to 65535
---
1
F500
0
Remote Input/Output States (Read Only)
1540
Remote Device States
0 to 65535
---
1
F500
0
1542
Remote Input States (4 items)
0 to 65535
---
1
F500
0
1550
Remote Devices Online
0 to 1
---
1
F126
0 (No)
1551
Remote Double-Point Status Input 1 State
0 to 3
---
1
F605
3 (Bad)
1552
Remote Double-Point Status Input 2 State
0 to 3
---
1
F605
3 (Bad)
1553
Remote Double-Point Status Input 3 State
0 to 3
---
1
F605
3 (Bad)
1554
Remote Double-Point Status Input 4 State
0 to 3
---
1
F605
3 (Bad)
1555
Remote Double-Point Status Input 5 State
0 to 3
---
1
F605
3 (Bad)
Platform Direct Input/Output States (Read Only)
15C0
Direct input states (6 items)
0 to 65535
---
1
F500
0
15C8
Direct outputs average message return time 1
0 to 65535
ms
1
F001
0
15C9
Direct outputs average message return time 2
0 to 65535
ms
1
F001
0
15CA
Direct inputs/outputs unreturned message count - Ch. 1
0 to 65535
---
1
F001
0
15CB
Direct inputs/outputs unreturned message count - Ch. 2
0 to 65535
---
1
F001
0
15D0
Direct device states
0 to 65535
---
1
F500
0
15D1
Reserved
0 to 65535
---
1
F001
0
15D2
Direct inputs/outputs CRC fail count 1
0 to 65535
---
1
F001
0
15D3
Direct inputs/outputs CRC fail count 2
0 to 65535
---
1
F001
0
Ethernet Fibre Channel Status (Read/Write)
1610
Ethernet primary fibre channel status
0 to 2
---
1
F134
0 (Fail)
1611
Ethernet secondary fibre channel status
0 to 2
---
1
F134
0 (Fail)
Data Logger Actuals (Read Only)
1618
Data logger channel count
0 to 16
channel
1
F001
0
1619
Time of oldest available samples
0 to 4294967295
seconds
1
F050
0
161B
Time of newest available samples
0 to 4294967295
seconds
1
F050
0
161D
Data logger duration
0 to 999.9
days
0.1
F001
0
Source Current (Read Only) (6 modules)
1800
Source 1 Phase A Current RMS
0 to 999999.999
A
0.001
F060
0
1802
Source 1 Phase B Current RMS
0 to 999999.999
A
0.001
F060
0
1804
Source 1 Phase C Current RMS
0 to 999999.999
A
0.001
F060
0
1806
Source 1 Neutral Current RMS
0 to 999999.999
A
0.001
F060
0
1808
Source 1 Phase A Current Magnitude
0 to 999999.999
A
0.001
F060
0
180A
Source 1 Phase A Current Angle
-359.9 to 0
degrees
0.1
F002
0
180B
Source 1 Phase B Current Magnitude
0 to 999999.999
A
0.001
F060
0
Table B–9: MODBUS MEMORY MAP (Sheet 3 of 53)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание UR Series C70
Страница 2: ......
Страница 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C70 Capacitor Bank Protection and Control System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 124: ...4 30 C70 Capacitor Bank Protection and Control System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 344: ...5 220 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 396: ...8 18 C70 Capacitor Bank Protection and Control System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 414: ...9 18 C70 Capacitor Bank Protection and Control System GE Multilin 9 1 OVERVIEW 9 THEORY OF OPERATION 9 ...
Страница 436: ...10 22 C70 Capacitor Bank Protection and Control System GE Multilin 10 4 SETTING EXAMPLE 10 APPLICATION OF SETTINGS 10 ...
Страница 547: ...GE Multilin C70 Capacitor Bank Protection and Control System B 79 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 548: ...B 80 C70 Capacitor Bank Protection and Control System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 586: ...D 10 C70 Capacitor Bank Protection and Control System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Страница 598: ...E 12 C70 Capacitor Bank Protection and Control System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...