GE Multilin
C70 Capacitor Bank Protection and Control System
B-67
APPENDIX B
B.4 MEMORY MAPPING
B
F125
ENUMERATION: ACCESS LEVEL
0 = Restricted; 1 = Command, 2 = Setting, 3 = Factory Service
F126
ENUMERATION: NO/YES CHOICE
0 = No, 1 = Yes
F127
ENUMERATION: LATCHED OR SELF-RESETTING
0 = Latched, 1 = Self-Reset
F128
ENUMERATION: CONTACT INPUT THRESHOLD
0 = 17 V DC, 1 = 33 V DC, 2 = 84 V DC, 3 = 166 V DC
F129
ENUMERATION: FLEXLOGIC TIMER TYPE
0 = millisecond, 1 = second, 2 = minute
F130
ENUMERATION: SIMULATION MODE
0 = Off. 1 = Pre-Fault, 2 = Fault, 3 = Post-Fault
F131
ENUMERATION: FORCED CONTACT OUTPUT STATE
0 = Disabled, 1 = Energized, 2 = De-energized, 3 = Freeze
F133
ENUMERATION: PROGRAM STATE
0 = Not Programmed, 1 = Programmed
F134
ENUMERATION: PASS/FAIL
0 = Fail, 1 = OK, 2 = n/a
F135
ENUMERATION: GAIN CALIBRATION
0 = 0x1, 1 = 1x16
F136
ENUMERATION: NUMBER OF OSCILLOGRAPHY RECORDS
0 = 31 x 8 cycles, 1 = 15 x 16 cycles, 2 = 7 x 32 cycles
3 = 3 x 64 cycles, 4 = 1 x 128 cycles
F137
ENUMERATION: USER-PROGRAMMABLE PUSHBUTTON
FUNCTION
0 = Disabled, 1 = Self-Reset, 2 = Latched
F138
ENUMERATION: OSCILLOGRAPHY FILE TYPE
0 = Data File, 1 = Configuration File, 2 = Header File
F140
ENUMERATION: CURRENT, SENS CURRENT, VOLTAGE,
DISABLED
0 = Disabled, 1 = Current 46 A, 2 = Voltage 280 V,
3 = Current 4.6 A, 4 = Current 2 A, 5 = Notched 4.6 A,
6 = Notched 2 A
F141
ENUMERATION: SELF TEST ERRORS
970
Breaker 3
971
Breaker 4
972
Breaker 5
973
Breaker 6
980
Breaker restrike 1
981
Breaker restrike 2
982
Breaker restrike 3
bitmask
element
Bitmask
Error
0
Any Self Tests
1
IRIG-B Failure
2
Port 1 Offline
3
Port 2 Offline
4
Port 3 Offline
5
Port 4 Offline
6
Port 5 Offline
7
Port 6 Offline
8
RRTD Communcations Failure
9
Voltage Monitor
10
FlexLogic Error Token
11
Equipment Mismatch
12
Process Bus Failure
13
Unit Not Programmed
14
System Exception
15
Latching Output Discrepancy
16
Ethernet Switch Fail
17
Maintenance Alert 01
18
SNTP Failure
19
---
20
Primary Ethernet Fail
21
Secondary Ethernet Fail
22
Temperature Monitor
23
Process Bus Trouble
24
Brick Trouble
25
Field RTD Trouble
26
Field TDR Trouble
Содержание UR Series C70
Страница 2: ......
Страница 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C70 Capacitor Bank Protection and Control System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 124: ...4 30 C70 Capacitor Bank Protection and Control System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 344: ...5 220 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 396: ...8 18 C70 Capacitor Bank Protection and Control System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 414: ...9 18 C70 Capacitor Bank Protection and Control System GE Multilin 9 1 OVERVIEW 9 THEORY OF OPERATION 9 ...
Страница 436: ...10 22 C70 Capacitor Bank Protection and Control System GE Multilin 10 4 SETTING EXAMPLE 10 APPLICATION OF SETTINGS 10 ...
Страница 547: ...GE Multilin C70 Capacitor Bank Protection and Control System B 79 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 548: ...B 80 C70 Capacitor Bank Protection and Control System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 586: ...D 10 C70 Capacitor Bank Protection and Control System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Страница 598: ...E 12 C70 Capacitor Bank Protection and Control System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...