5-175
5 SETTINGS
5.7 CONTROL ELEMENTS
5
are used for security, the appropriate filtering logic possibly including discrepancy alarming can be programmed in
FlexLogic™, and the resulting virtual output can be configured under this setting.
•
CAP 1 TRIP SEAL-IN DELAY
: Sets a maximum trip seal-in duration for where the
CAP 1 BKR OPEN 52B
setting is not
configured or fails to operate.
•
CAP 1 REMOTE CLOSE
: Similar to the
CAP 1 REMOTE OPEN
setting, but closes the breaker.
•
CAP 1 LOCAL CLOSE
: Similar to the
CAP 1 LOCAL OPEN
setting, but closes the breaker.
•
CAP 1 AUTO CLOSE
: Similar to the
CAP 1 AUTO OPEN
setting, but closes the breaker.
•
CAP 1 BKR CLSD 52a
: Similar to the
CAP 1 BKR OPEN 52B
setting, but cancels the close seal-in, and is expected to be
set to a contact that is closed when the breaker is closed. The selected operand also triggers the
CAP 1 DISCHARGE
TIME
. When both 52a and 52b contacts are used for security, the appropriate filtering logic possibly including discrep-
ancy alarming can be programmed in FlexLogic™, and the resulting virtual output can be configured under this setting.
•
CAP 1 CLOSE SEAL-IN DELAY
: Sets a maximum close seal-in duration for where the
CAP BKR CLOSED 52A
setting is
not configured or fails to operate.
•
CAP 1 DISCHARGE TIME
: Sets a time delay that inhibits closing after the bank has been switched out-of-service (the
CAP BKR CLOSE 52A
setting goes low or trip command terminates) until the bank has had time to discharge any trapped
charge. The correct value for this setting depends on the specifics of the capacitor installation.
•
CAP 1 BKR CLOSE BLK
: Selects a FlexLogic™ operand that triggers the
CAP 1 BKR CLOSE
interlock logic. Its signal
is expected to originate from capacitor breaker trips external to the relay, and thus not otherwise able to block relay
closing (for example, from the opposite group's capacitor protection).
•
CAP 1 CLS OVERRIDE
: Selects a FlexLogic™ operand that overrides all inhibits for the breaker close command and
allows the
CLOSE
command to be issued from any source as per the logic diagram.
Содержание UR Series C70
Страница 2: ......
Страница 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C70 Capacitor Bank Protection and Control System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 124: ...4 30 C70 Capacitor Bank Protection and Control System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 344: ...5 220 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 396: ...8 18 C70 Capacitor Bank Protection and Control System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 414: ...9 18 C70 Capacitor Bank Protection and Control System GE Multilin 9 1 OVERVIEW 9 THEORY OF OPERATION 9 ...
Страница 436: ...10 22 C70 Capacitor Bank Protection and Control System GE Multilin 10 4 SETTING EXAMPLE 10 APPLICATION OF SETTINGS 10 ...
Страница 547: ...GE Multilin C70 Capacitor Bank Protection and Control System B 79 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 548: ...B 80 C70 Capacitor Bank Protection and Control System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 586: ...D 10 C70 Capacitor Bank Protection and Control System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Страница 598: ...E 12 C70 Capacitor Bank Protection and Control System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...