5-104
C70 Capacitor Bank Protection and Control System
GE Multilin
5.5 FLEXLOGIC™
5 SETTINGS
5
5.5.8 NON-VOLATILE LATCHES
PATH: SETTINGS
ÖØ
FLEXLOGIC
ÖØ
NON-VOLATILE LATCHES
Ö
LATCH 1(16)
The non-volatile latches provide a permanent logical flag that is stored safely and will not reset upon reboot after the relay
is powered down. Typical applications include sustaining operator commands or permanently block relay functions, such as
Autorecloser, until a deliberate interface action resets the latch. The settings element operation is described below:
•
LATCH 1 TYPE
: This setting characterizes Latch 1 to be Set- or Reset-dominant.
•
LATCH 1 SET
: If asserted, the specified FlexLogic™ operands 'sets' Latch 1.
•
LATCH 1 RESET
: If asserted, the specified FlexLogic™ operand 'resets' Latch 1.
Figure 5–45: NON-VOLATILE LATCH OPERATION TABLE (N = 1 to 16) AND LOGIC
LATCH 1
LATCH 1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
LATCH 1 TYPE:
Reset Dominant
Range: Reset Dominant, Set Dominant
MESSAGE
LATCH 1 SET:
Off
Range: FlexLogic™ operand
MESSAGE
LATCH 1 RESET:
Off
Range: FlexLogic™ operand
MESSAGE
LATCH 1
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
LATCH 1
EVENTS: Disabled
Range: Disabled, Enabled
842005A1.CDR
LATCH 1 FUNCTION:
LATCH 1 TYPE:
LATCH 1 SET:
LATCH 1 SET:
RUN
SET
RESET
SETTING
SETTING
SETTING
SETTING
FLEXLOGIC OPERANDS
Disabled=0
Off=0
Off=0
Enabled=1
LATCH 1 ON
LATCH 1 OFF
LATCH N
TYPE
LATCH N
SET
LATCH N
RESET
LATCH N
ON
LATCH N
OFF
Reset
Dominant
ON
OFF
ON
OFF
OFF
OFF
Previous
State
Previous
State
ON
ON
OFF
ON
OFF
ON
OFF
ON
Set
Dominant
ON
OFF
ON
OFF
ON
ON
ON
OFF
OFF
OFF
Previous
State
Previous
State
OFF
ON
OFF
ON
Содержание UR Series C70
Страница 2: ......
Страница 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C70 Capacitor Bank Protection and Control System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 124: ...4 30 C70 Capacitor Bank Protection and Control System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 344: ...5 220 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 396: ...8 18 C70 Capacitor Bank Protection and Control System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 414: ...9 18 C70 Capacitor Bank Protection and Control System GE Multilin 9 1 OVERVIEW 9 THEORY OF OPERATION 9 ...
Страница 436: ...10 22 C70 Capacitor Bank Protection and Control System GE Multilin 10 4 SETTING EXAMPLE 10 APPLICATION OF SETTINGS 10 ...
Страница 547: ...GE Multilin C70 Capacitor Bank Protection and Control System B 79 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 548: ...B 80 C70 Capacitor Bank Protection and Control System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 586: ...D 10 C70 Capacitor Bank Protection and Control System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Страница 598: ...E 12 C70 Capacitor Bank Protection and Control System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...