GE Multilin
C70 Capacitor Bank Protection and Control System
B-45
APPENDIX B
B.4 MEMORY MAPPING
B
AFDB
...Repeated for IEC 61850 GGIO4 analog input 30
AFE2
...Repeated for IEC 61850 GGIO4 analog input 31
AFE9
...Repeated for IEC 61850 GGIO4 analog input 32
IEC 61850 Logical Node Name Prefixes (Read/Write Setting)
AB30
IEC 61850 Logical Node LPHD1 Name Prefix
0 to 65534
---
1
F206
(None)
AB33
IEC 61850 Logical Node PIOCx Name Prefix (72 items)
0 to 65534
---
1
F206
(None)
AC0B
IEC 61850 Logical Node PTOCx Name Prefix (24 items)
0 to 65534
---
1
F206
(None)
AC53
IEC 61850 Logical Node PTUVx Name Prefix (12 items)
0 to 65534
---
1
F206
(None)
AC77
IEC 61850 Logical Node PTOVx Name Prefix (8 items)
0 to 65534
---
1
F206
(None)
AC8F
IEC 61850 Logical Node PDISx Name Prefix (10 items)
0 to 65534
---
1
F206
(None)
ACAD
IEC 61850 Logical Node RRBFx Name Prefix (24 items)
0 to 65534
---
1
F206
(None)
ACF5
IEC 61850 Logical Node RPSBx Name Prefix
0 to 65534
---
1
F206
(None)
ACF8
IEC 61850 Logical Node RRECx Name Prefix (6 items)
0 to 65534
---
1
F206
(None)
AD0A
IEC 61850 Logical Node MMXUx Name Prefix (6 items)
0 to 65534
---
1
F206
(None)
AD1C
IEC 61850 Logical Node GGIOx Name Prefix (4 items)
0 to 65534
---
1
F206
(None)
AD28
IEC 61850 Logical Node RFLOx Name Prefix (5 items)
0 to 65534
---
1
F206
(None)
AD37
IEC 61850 Logical Node XCBRx Name Prefix (2 items)
0 to 65534
---
1
F206
(None)
AD3D
IEC 61850 Logical Node PTRCx Name Prefix (2 items)
0 to 65534
---
1
F206
(None)
AD43
IEC 61850 Logical Node PDIFx Name Prefix (4 items)
0 to 65534
---
1
F206
(None)
AD4F
IEC 61850 Logical Node MMXNx Name Prefix (37 items)
0 to 65534
---
1
F206
(None)
IEC 61850 GOOSE/GSSE Configuration (Read/Write Setting)
B01C
Default GOOSE/GSSE Update Time
1 to 60
s
1
F001
60
B01D
IEC 61850 GSSE Function (GsEna)
0 to 1
---
1
F102
1 (Enabled)
B013
IEC 61850 GSSE ID
---
---
---
F209
“GSSEOut”
B03F
IEC 61850 GOOSE Function (GoEna)
0 to 1
---
1
F102
0 (Disabled)
B040
IEC 61850 GSSE Destination MAC Address
---
---
---
F072
0
B043
IEC 61850 Standard GOOSE ID
---
---
---
F209
“GOOSEOut”
B064
IEC 61850 Standard GOOSE Destination MAC Address
---
---
---
F072
0
B067
IEC 61850 GOOSE VLAN Transmit Priority
0 to 7
---
1
F001
4
B068
IEC 61850 GOOSE VLAN ID
0 to 4095
---
1
F001
0
B069
IEC 61850 GOOSE ETYPE APPID
0 to 16383
---
1
F001
0
B06A
Reserved (2 items)
0 to 1
---
1
F001
0
IEC 61850 Server Configuration (Read/Write Settings/Commands)
B06C
TCP Port Number for the IEC 61850 / MMS Protocol
1 to 65535
---
1
F001
102
B06D
IEC 61850 Logical Device Name
---
---
---
F213
“IECName”
B07D
IEC 61850 Logical Device Instance
---
---
---
F213
“LDInst”
B08D
IEC 61850 LPHD Location
---
---
---
F204
“Location”
B0B5
Include non-IEC 61850 Data
0 to 1
---
1
F102
0 (Disabled)
B06B
IEC 61850 Server Data Scanning Function
0 to 1
---
1
F102
0 (Disabled)
B0B7
Reserved (15 items)
IEC 61850 MMXU Deadbands (Read/Write Setting) (6 modules)
B0C0
IEC 61850 MMXU TotW Deadband 1
0.001 to 100
%
0.001
F003
10000
B0C2
IEC 61850 MMXU TotVAr Deadband 1
0.001 to 100
%
0.001
F003
10000
B0C4
IEC 61850 MMXU TotVA Deadband 1
0.001 to 100
%
0.001
F003
10000
B0C6
IEC 61850 MMXU TotPF Deadband 1
0.001 to 100
%
0.001
F003
10000
B0C8
IEC 61850 MMXU Hz Deadband 1
0.001 to 100
%
0.001
F003
10000
B0CA
IEC 61850 MMXU PPV.phsAB Deadband 1
0.001 to 100
%
0.001
F003
10000
B0CC
IEC 61850 MMXU PPV.phsBC Deadband 1
0.001 to 100
%
0.001
F003
10000
B0CE
IEC 61850 MMXU PPV.phsCA Deadband 1
0.001 to 100
%
0.001
F003
10000
B0D0
IEC 61850 MMXU PhV.phsADeadband 1
0.001 to 100
%
0.001
F003
10000
B0D2
IEC 61850 MMXU PhV.phsB Deadband 1
0.001 to 100
%
0.001
F003
10000
B0D4
IEC 61850 MMXU PhV.phsC Deadband 1
0.001 to 100
%
0.001
F003
10000
B0D6
IEC 61850 MMXU A.phsA Deadband 1
0.001 to 100
%
0.001
F003
10000
B0D8
IEC 61850 MMXU A.phsB Deadband 1
0.001 to 100
%
0.001
F003
10000
Table B–9: MODBUS MEMORY MAP (Sheet 38 of 53)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание UR Series C70
Страница 2: ......
Страница 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C70 Capacitor Bank Protection and Control System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 124: ...4 30 C70 Capacitor Bank Protection and Control System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 344: ...5 220 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 396: ...8 18 C70 Capacitor Bank Protection and Control System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 414: ...9 18 C70 Capacitor Bank Protection and Control System GE Multilin 9 1 OVERVIEW 9 THEORY OF OPERATION 9 ...
Страница 436: ...10 22 C70 Capacitor Bank Protection and Control System GE Multilin 10 4 SETTING EXAMPLE 10 APPLICATION OF SETTINGS 10 ...
Страница 547: ...GE Multilin C70 Capacitor Bank Protection and Control System B 79 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 548: ...B 80 C70 Capacitor Bank Protection and Control System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 586: ...D 10 C70 Capacitor Bank Protection and Control System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Страница 598: ...E 12 C70 Capacitor Bank Protection and Control System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...