GE Multilin
C70 Capacitor Bank Protection and Control System
B-15
APPENDIX B
B.4 MEMORY MAPPING
B
Modbus file transfer values (read only)
3200
Character position of current block within file
0 to 4294967295
---
1
F003
0
3202
Size of currently-available data block
0 to 65535
---
1
F001
0
3203
Block of data from requested file (122 items)
0 to 65535
---
1
F001
0
Event recorder actual values (read only)
3400
Events Since Last Clear
0 to 4294967295
---
1
F003
0
3402
Number of Available Events
0 to 4294967295
---
1
F003
0
3404
Event Recorder Last Cleared Date
0 to 4294967295
---
1
F050
0
Event recorder commands (read/write)
3406
Event Recorder Clear Command
0 to 1
---
1
F126
0 (No)
Neutral current unbalance commands and actual values (read/write unless noted, 3 modules)
3410
Neutral current unbalance automatic setting function
0 to 2
---
1
F092
0 (Disabled)
3411
Neutral current unbalance apply magnitude
0 to 1
---
1
F126
0 (No)
3412
Neutral current unbalance apply angle
0 to 1
---
1
F126
0 (No)
3413
60N apply magnitude actual value (read only)
0 to 0.1500
---
0.0001
F003
0
3415
60N apply angle actual value (read only)
0 to 359
°
1
F003
0
3417
...Repeated for neutral current unbalance 2
341E
...Repeated for neutral current unbalance 3
Neutral voltage unbalance commands and actual values (read/write unless noted, 3 modules)
3430
Neutral voltage unbalance automatic setting function
0 to 2
---
1
F092
0 (Disabled)
3431
59NU XA/XB ratio actual value (read only)
0 to 9.9999
---
0.0001
F003
0
3433
Neutral voltage unbalance auto-set XA/XB ratio
0 to 1
---
1
F126
0 (No)
3434
59NU XA/XC ratio actual value (read only)
0 to 9.9999
---
0.0001
F003
0
3436
Neutral voltage unbalance auto-set XA/XC ratio
0 to 1
---
1
F126
0 (No)
3437
...Repeated for neutral voltage unbalance 2
343E
...Repeated for neutral voltage unbalance 3
Phase current unbalance commands and actual values (read/write unless noted, 3 modules)
3450
Phase current unbalance automatic setting function
0 to 2
---
1
F092
0 (Disabled)
3451
Phase current unbalance Ka actual value (read only)
–0.1000 to 0.1000
---
0.0001
F004
0
3453
Phase current unbalance auto-set Ka
0 to 1
---
1
F126
0 (No)
3454
Phase current unbalance Kb actual value (read only)
–0.1000 to 0.1000
---
0.0001
F004
0
3456
Phase current unbalance auto-set Kb
0 to 1
---
1
F126
0 (No)
3457
Phase current unbalance Kc actual value (read only)
–0.1000 to 0.1000
---
0.0001
F004
0
3459
Phase current unbalance auto-set Kc
0 to 1
---
1
F126
0 (No)
345A
...Repeated for phase current unbalance 2
3464
...Repeated for phase current unbalance 3
Voltage differential commands and actual values (read/write unless noted, 3 modules)
3470
Voltage differential automatic setting function
0 to 2
---
1
F092
0 (Disabled)
3471
Voltage differential Ka actual value (read only)
0 to 99.9999
---
0.0001
F003
0
3473
Voltage differential auto-set Ka
0 to 1
---
1
F126
0 (No)
3474
Voltage differential Kb actual value (read only)
0 to 99.9999
---
0.0001
F003
0
3476
Voltage differential auto-set Kb
0 to 1
---
1
F126
0 (No)
3477
Voltage differential Kc actual value (read only)
0 to 99.9999
---
0.0001
F003
0
3479
Voltage differential auto-set Kc
0 to 1
---
1
F126
0 (No)
347A
...Repeated for voltage differential 2
3484
...Repeated for voltage differential 3
DCMA Input Values (Read Only) (24 modules)
34C0
DCMA Inputs 1 Value
-9999999 to 9999999
---
1
F004
0
34C2
DCMA Inputs 2 Value
-9999999 to 9999999
---
1
F004
0
34C4
DCMA Inputs 3 Value
-9999999 to 9999999
---
1
F004
0
34C6
DCMA Inputs 4 Value
-9999999 to 9999999
---
1
F004
0
34C8
DCMA Inputs 5 Value
-9999999 to 9999999
---
1
F004
0
34CA
DCMA Inputs 6 Value
-9999999 to 9999999
---
1
F004
0
34CC
DCMA Inputs 7 Value
-9999999 to 9999999
---
1
F004
0
Table B–9: MODBUS MEMORY MAP (Sheet 8 of 53)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание UR Series C70
Страница 2: ......
Страница 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C70 Capacitor Bank Protection and Control System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 124: ...4 30 C70 Capacitor Bank Protection and Control System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 344: ...5 220 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 396: ...8 18 C70 Capacitor Bank Protection and Control System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 414: ...9 18 C70 Capacitor Bank Protection and Control System GE Multilin 9 1 OVERVIEW 9 THEORY OF OPERATION 9 ...
Страница 436: ...10 22 C70 Capacitor Bank Protection and Control System GE Multilin 10 4 SETTING EXAMPLE 10 APPLICATION OF SETTINGS 10 ...
Страница 547: ...GE Multilin C70 Capacitor Bank Protection and Control System B 79 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 548: ...B 80 C70 Capacitor Bank Protection and Control System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 586: ...D 10 C70 Capacitor Bank Protection and Control System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Страница 598: ...E 12 C70 Capacitor Bank Protection and Control System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...