GE Multilin
C70 Capacitor Bank Protection and Control System
5-137
5 SETTINGS
5.6 GROUPED ELEMENTS
5
The relay allows manual setting of the inherent unbalance factor or automatic setting via a dedicated command. For addi-
tional information, refer to the
Theory of operation
and
Application of settings
chapters.
Figure 5–62: NEUTRAL CURRENT UNBALANCE CONNECTIONS
The following settings are available. The settings shown below are for the neutral current unbalance 1 element. The same
descriptions apply to the neutral current unbalance 2 and 3 elements.
•
NTRL CUR UNBALCE 1 BANK SOURCE
: This setting indicates the signal source that signifies the split-phase neutral
current in its ground current channel. At minimum the ground channel of this source must be set. If the factor compen-
sating for inherent bank unbalance is set above zero signalling the intent of using the compensation, the phase cur-
rents of this source must be configured as well. Without the phase currents configured under this source, the function
would run only if the magnitude of the inherent unbalance factor is set to zero.
To improve accuracy, a relatively low-ratio window CT can be used for instrumentation of the split-phase neutral cur-
rent, and be wired to a 1 A or even sensitive ground relay input for extra sensitivity. CT primary and secondary ratings
are entered under a separate menu. Directionality of wiring of the split-phase current is not important for proper func-
tioning of the feature as long as the angle of the factor compensating for the inherent unbalance is set appropriately.
•
NTRL CUR UNBALCE 1 K MAG
: This setting defines magnitude of the factor compensating for the inherent unbal-
ance of the bank. Under balanced conditions, the amount of the spill current measured in the neutral connection
between the banks is proportional to the positive-sequence component of the total current of the two banks. This set-
ting defines the magnitude of the proportionality factor. Quality of balancing the bank with a given value of this setting
can be viewed under
ACTUAL VALUES
menu. An automatic setting procedure is available via the
COMMANDS
menu to
calculate the compensating factor automatically. Setting the compensating factor to zero effectively disables the com-
pensation. If further the slope is set to zero as well, this feature becomes a plain overcurrent element responding to the
neutral split-phase current.
•
NTRL CUR UNBALCE 1 K ANG
: This setting defines angle of the factor compensating for the inherent unbalance of
the bank. Under balanced conditions, the amount of the spill current measured in the neutral connection between the
C70 CAPACITOR BANK RELAY
60N
BANK
SOURCE
Neutral
CT bank
Ground
CT
Regular, preferably
low-ratio CT for
ungrounded banks
Window / core-
balance CTs for
grounded banks
834735A1.CDR
Содержание UR Series C70
Страница 2: ......
Страница 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C70 Capacitor Bank Protection and Control System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 124: ...4 30 C70 Capacitor Bank Protection and Control System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 344: ...5 220 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 396: ...8 18 C70 Capacitor Bank Protection and Control System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 414: ...9 18 C70 Capacitor Bank Protection and Control System GE Multilin 9 1 OVERVIEW 9 THEORY OF OPERATION 9 ...
Страница 436: ...10 22 C70 Capacitor Bank Protection and Control System GE Multilin 10 4 SETTING EXAMPLE 10 APPLICATION OF SETTINGS 10 ...
Страница 547: ...GE Multilin C70 Capacitor Bank Protection and Control System B 79 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 548: ...B 80 C70 Capacitor Bank Protection and Control System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 586: ...D 10 C70 Capacitor Bank Protection and Control System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Страница 598: ...E 12 C70 Capacitor Bank Protection and Control System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...